Model AT-2004 Cable Tracing System includes receiver, load signal generator, transmitter, clamp-on transmitter accessory, cordsets and adapter. All components are fully fused, protected and intrinsically safe; and fit into a foam-lined carrying case that includes condensed operating instructions in its lid.
Model R2000 Receiver has two detectors in its tip which are tuned to pick up the electromagnetic signals ('short' mode) or electrostatic signals ('open' mode) generated by other components. The LEDs and sensitivity settings indicate the relative signal strength to allow easy detection of the signal source.
Model S2600 Load Signal Generator, when connected to an energized line, will draw a rapidly fluctuating current pulse from the source, causing the power line to emit an electromagnetic
signal which is detected by the R2000 Receiver in the 'short' mode. These devices allow tracing of line-side conductors without power interruption or interference.
The T2200 Transmitter injects a signal into an unenergized conductor. If the conductor is broken (open), no current will flow, so the signal is present as a voltage pulse, which is detected along
the conductor's length by the R2000's electrostatic detector ('open' mode). The signal will stop at the open.
When the A2201 Inductive Clamp is clamped around the energized line and plugged into the T2200 Transmitter, it will induce a signal onto the downstream (load) side to enable identification of equipment on that circuit.
Applications:
Trace conductors buried up to 13 feet
Trace and identify load-side equipment from the circuit breaker while energized
Trace line-side wiring without power interruption on circuits from 9 to 600 Volts AC or DC
Trace open wires for over a mile
Trace wire in conduit, or even the conduit itself
Locate ground faults and shorts
Identify individual wires in a bundle
Specifications:
R2000 RECEIVER
Detectors: Electromagnetic coil pickup for short mode; Electrostatic plate pickup for open mode
Sensitivity: Switchable x1, x10, x100 coarse gain adjustment with 0 - 10 fine adjustment
Short Mode Performance: >20' in air under test conditions
Open Mode Performance: >12' in air under test conditions
60 Hz Rejection: 120 dB
Display: 10 LEDs with chroma filter lens
Power Supply: 9V alkaline battery
S2600 LOAD SIGNAL GENERATOR
Operating Voltage: 9 - 600 VAC or VDC
Operating Frequency: 32.768 kHz
Duty Cycle: Transmits two pulses with a duration of 0.0625 each every 0.5 secs.
Current Output: Low mode: 35 mA peak, 4 mA avg.; High mode: 70 mA peak, 6 mA avg.
Fuse: Fast acting 250 mA @ 660 V
2200 TRANSMITTER
Operating Frequency: 32.768 kHz
Duty Cycle: Transmits two pulses with a duration of 0.0625 each every 0.5 secs.
Signal Output: 9 V supply 24 V supply
High Setting: 1 A, 31 V 3 A, 105V
Med Setting: 1.8 A, 13 V 6 A, 45 V
Low Setting: 3 A, 6.5 V 10 A, 22 V
Fuse: Fast acting 2 A@ 250 V 3AG, 1/4" x 1 1/4"
Power Supply: 9V alkaline battery; 24V jack will accept battery pack (B2024 or B2025)
A2201 CLAMP-ON TRANSMITTER ACCESSORY
Operating Frequency: 32.768 kHz supplied by T2200 Transmitter
Case Breakdown Voltage: 3000 V
Max. Wire Size: 2000 MCM or 2" dia. cable
Power Supply: Powered from T2200 Transmitter
GENERAL SYSTEM
Operating Temperature: 0 - 120°F (-17.8 - 48.9°C)
Dimensions (HWD): 4" x 15.5" x 11" (10.2 x 39.4 x 27.9cm)
Weight: 4 lbs. 5 oz. (1.95 kg)