Series EBT721 Balometer Kits

The EBT721 Balometer Electronic Balancing Tool features a detachable multi-purpose digital manometer that can be used with a variety of common test and balance tools, such as pitot, air foil, temperature, relative humidity probes or a 16-point velocity matrix.

Features:

  • Detachable manometer can be used with optional probes
  • Reads in. H2O, ft H2O, psi, in. Hg, mm Hg, m H2O, kPa, mm Hg, bar
  • Displays Min, Max and Average of up to 1000 readings
  • Stores up to 1000 readings with time and date stamp
  • Battery operated
  • Includes CompuDat software to download data to PC
  • Shipped complete with manometer, 2[base '] x 2[base '] air capture hood/ frame/base, 4 "AA" size rechargeable NiMH batteries, external battery charger, 18" pitot probe, 2 static pressure probes, 16 ft. neoprene tubing, wheeled carrying case, CompuDat software and manual

    Specifications:

    RANGE

  • Differential Pressure: ±15 in. H2O (3735 Pa)
  • Absolute Pressure: 15 to 40 in Hg (356 to 1016 Hg)
  • Air Velocity: 25 to 8,000 fpm (0.125 to 40 m/s) pitot tube; 25 to 5,000 fpm (0.125 to 25 m/s) air flow probe; 25 to 2,500 fpm (0.125 to 12.5 m/s) velocity matrix
  • Air Volume: 25 to 2,500 ft3/m (42 to 4250 m3/h)
  • Humidity: 0 to 95% RH (optional probe)
  • Temperature -40 to 250°F (-40 to 121°C) probe dependent

    RESOLUTION

  • Differential Pressure: 0.00001 in. H2O (0.001 Pa)
  • Absolute Pressure: 0.001 in. Hg (1 mmHg)
  • Air Velocity: 0.1 fpm (0.1 m/s)
  • Air Volume: 0.1 ft3/m (0.1 m3/h)
  • Humidity: 0.1% RH
  • Temperature 0.1°F (0.1°C)

    ACCURACY

  • Differential Pressure: ±2% rdg. ±0.001 in. H2O (0.025mm H2O)
  • Absolute Pressure: ±2% rdg. ±0.001 in. Hg
  • Air Velocity: ±3% rdg. ±7 fpm (0.04 m/s) 25 to 8,000 fpm (all velocity probes) > 50 fpm
  • Air Volume: ±3% rdg. ±7 ft3/m 25 to 2,500 ft3/m
  • Humidity: ±3% RH
  • Temperature ±0.5°F (0.3°C) 32 to 160°F (0 to 71°C); ±1.0°F (0.6°C) -40 to 32°F (-40 to 0°C) & 160 to 250°F (71 to 121°C)

    GENERAL

  • Response Time: 2 to 8 seconds
  • Sampling Interval: Continuous or user selectable (10 to 600 seconds)
  • Display: 6-digit, 0.75" high LCD, multi-line, sectored, multiple symbolic icons, with backlight
  • Power Supply: 4 x AA-size rechargeable NiMH batteries
  • Battery Life: Minimum of 12 hours
  • Dimensions: 7.4 x 4.5 x 2.3" (188 x 114 x 58mm)
  • Weight: 7.4 lb (3.4 kg)

  • Product Info

    Product Name
    Product Number
    Price $CAN
    Add
    Balometer Kit EBT721-A1EBT721-A1 $3073.00 add to basket
    Balometer Kit with 16-point Velocity Matrix EBT721-X1EBT721-X1 $3450.00 add to basket
    Balometer Kit with 16-point Velocity Matrix and Temperature Probe EBT721-01EBT721-01 $3575.00 add to basket
    Balometer Kit with 16-point Velocity Matrix, Temperature and Air Flow Probe EBT721-Z1EBT721-Z1 $4078.00 add to basket